The acceptable solution requires that all floors be fire separations, except when that floor is either an ‘intermediate floor’ within a firecell or the lowest floor above an unoccupied sub-floor space. Where floors are fire serrations, then fire rating is required only on the underside and the rating is that which applies to the firecell directly below the floor.
An ‘Intermediate’ floor is an upper floor within a firecell which is permitted not to be fire separated from the floor below.
11.2 scope of manual - fire resistance calculation of tray flooring
11.6 mezzanines as intermediate floors (model type 4)
11.7 compliance with fire resistance requirements
11.8 - 30 minute fire rated composite floor
11.9 positive reinforced fire rated slabs
11.10 negatively reinforced fire rated slabs
11.11 negative reinforcement calculation
11.12 “slab specification” with regard to negative reinforcement calculation
11.13 loadings used in negative reinforcement tables
11.14 live loadings / fire ratings used
11.15 negative reinforcement tables